Turbo PMAC2 VME Hardware Reference
Base Board Connector Pinouts 29
P2/JMACHA (96-Pin
Header) Continued
Front View
Pin# Row A Row B
(Format A)
Row B
(Format B)
Row C
26 PWMABOT2/ DAC2A VD27* CHT4 PWMABOT4/ DAC4A
27 PWMBTOP2/ DAC_STB2 VD28* USER2 PWMBTOP4/ DAC_STB4
28 PWMBBOT2/ DAC2B VD29* USER4 PWMBBOT4/ DAC4B
29 PWMCTOP2/ DIR2 VD30* ADC_DAA2 PWMCTOP4/ DIR4
30 PWMCBOT2/ PULSE2 VD31* ADC_DAA4 PWMCBOT4/ PULSE4
31 GND GND ADC_DAB2 GND
32 +5V +5V ADC_DAB4 +5V
Note: Format A for the B-row will be used if E7A-H, E8A-H, E9A-H, and E10A-H connect pins 2 and 3. This
format must be used for a 32-bit VME system. Format B for the B-row will be used if these jumpers connect pins 1
and 2. This format is not compatible with 32-bit VME systems.
* Not used
TB1 (2/4-Pin Terminal Block)
This terminal block can be used to provide the input for the power supply for the circuits on the PMAC2
board when it is not in a bus configuration. When the PMAC2 is in a bus configuration, these supplies
automatically come through the bus connector from the bus power supply; in this case, this terminal block
should not be used.
Pin# Symbol Function Description Notes
1 GND Common Reference Voltage
2 +5V Input Positive Supply Voltage Supplies all PMAC digital circuits
3 +12V Input Positive Supply Voltage +12V to +15V; not required on-board;
used on j1 to supply analog inputs
4 -12V Input Negative Supply Voltage -12V to –15V; required for opt-12 ADCs;
used on J1 to supply analog inputs
Note: Unless Option 12 (Analog-to-Digital Converters) is included on the board, only pins 1 and 2 may be provided
on this terminal block.
TB2 (4-Pin Terminal Block)
This terminal block provides the output for PMAC2’s watchdog timer relay, both normally open and
normally closed contacts.
Pin# Symbol Function Description Notes
1 WD_NC Output Watchdog Relay Out Normally closed
2 COM Input Watchdog Return +V or 0V
3 WD_NO Output Watchdog Relay Out Normally open
4 COM Input Watchdog Return +V or 0V
Note: The normally closed relay contact is open while PMAC2 is operating properly – it has power and the
watchdog timer is not tripped – and closed when the PMAC2 is not operating properly – either it has lost power or
the watchdog timer has tripped. The normally open relay contact is closed while PMAC2 is operating properly and
open when PMAC2 is not operating properly.