Advantage 900 Remote Operator Pendant
HARDWARE SETUP
7
HARDWARE SETUP
The Advantage 900 Remote Operator Pendant and Relay Board communication jumper settings
are configured at the factory depending on the communication format (USB2.0 or Bluetooth).
The Remote Operator Pendant jumpers should be left in their factory-supplied state and should
not require modification. They are described here for reference and troubleshooting purposes
only.
The behavior of the Emergency Stop circuitry on the Relay Board may be modified depending on
the settings of Relay Board jumpers E3, E4, E5, and E6. Refer to the example wiring diagrams in
Appendix B for more information.
Jumper Configuration
Advantage 900 Remote Pendant – (P/N: 300-603812-10x)
E POINT & PHYSICAL
LAYOUT
DESCRIPTION Cabled
USB2.0
Wireless
BlueTooth
E1
Factory Programming.
ON ON
E2
Supplies +5VDC power
through USB cable when
present.
ON
OFF
E3
Supplies +5VDC power
through factory programming
cable.
OFF
OFF
E4
Voltage monitor disable
jumper. When removed a
battery voltage drop below
+3VDC will cause the pendant
to shut down. Must be present
for cabled version.
ON
OFF
E5
Factory troubleshooting
jumper. Bluetooth signal
detection.
ON ON
E6
Factory troubleshooting
jumper. +5VDC bypass.
OFF
OFF